he 2-channel temperature measuring amplifier IMX12-TI01-2RTDR-2I-CPR/24VDC/CC

has inputs for: RTDs acc. to IEC 60751, DIN

43760, GOST 6651-94 (2, 3 and 4-wire) and

resistors 0…5 kò (2, 3 and 4-wire).

The device is configured via the PC interface.

The current outputs can be set to 0/4 … 20

mA and as source or sink.

A green LED indicates operational readiness.

A fault in the input circuit leads to a flashing

red LED according to NE44, an internal error

to a steady red LED. The fault current can be

adjusted to 21.5 mA.

The device can be used in safety circuits up

to SIL2 (high and low demand according to

IEC 61508) and meets the requirements of

NE21. It is equipped with removable screw

terminals. The device can be powered from a

power bridge that also transmits a collective

fault signal.

The device can be used in safety circuits up to

SIL 2 (high and low demand according to IEC

61508) (hardware fault tolerance HFT = 0).

The device is equipped with removable

spring-type terminals.

■ Input circuits monitored for wire-break and

short-circuit

■ Parameterized via PC

■ Complete galvanic isolation

■ Input reverse-polarity protected

■ Removable spring type terminals

■ Power bridge (connector incl. in delivery)

■ ATEX, IECEx, cFM,cUL, NEPSI, INMETRO, Kosha, TR CU EAC CMI

■ Installation in zone 2

■ SIL 2