功能描述 | Temperature measuring amplifier 2-channel |
文件大小 |
383.97 Kbytes |
頁(yè)面數(shù)量 |
5 頁(yè) |
生產(chǎn)廠商 | Turck Inc. |
企業(yè)簡(jiǎn)稱 |
TURCK【圖爾克】 |
中文名稱 | 德國(guó)圖爾克集團(tuán)公司官網(wǎng) |
原廠標(biāo)識(shí) | |
數(shù)據(jù)手冊(cè) | |
更新時(shí)間 | 2024-11-2 9:50:00 |
100003646規(guī)格書詳情
The temperature transducer IM12-
TI01-2RTDR-2I-CPR/24VDC/CC transmits
temperature-dependent measured values galvanically isolated. The devices are suitable for
operation in zone 2.
The 2-channel device has two inputs for
RTDs acc. to IEC 60751, DIN 43760,
GOST 6651-94 (2-, 3- and 4-wire) as well as
resistors 0…5 kò (2-, 3- and 4-wire). Two
0/4…20 mA current outputs are available on
the output side. The device can be powered
from a power bridge that also transmits a collective fault signal.
The device is parameterized via FDT and
IODD with a PC. The current outputs can be
set (either as source or sink) to 0/4…20 mA.
The inputs can be freely assigned to the outputs. In accordance with the parameterization
(I1, I2, I1 - I2 or I2 - I1), the input signals are
output as a 0/4…20 mA normalized current
signal.
The devices have a green power LED (Pwr)
and a red LED to indicate internal faults. For
each input circuit there is a yellow and a red
status LED. A fault in the input circuit leads
to a flashing red LED according to NE44, an
internal error to a steady red LED. The fault
current can be adjusted to 21.5
mA.
The device can be used in safety circuits up to
SIL2 (high and low demand according to IEC
61508) and meets the requirements of NE21.
It is equipped with removable spring type terminals.
The device can be used in safety circuits up to
SIL 2 (high and low demand according to IEC
61508) (hardware fault tolerance HFT = 0).
The device is equipped with removable
spring-type terminals.
■ Input circuits monitored for wire break and
short circuit
■ Parameterized via PC
■ Complete galvanic isolation
■ Removable spring type terminals
■ Power bridge (connector incl. in delivery)
■ ATEX use in Zone 2, cUL
■ SIL 2